To test the air conditioning, the outside temperature should be
above 60° for 48 hours (some manufacturers recommend 65°). If you
turn the air conditioning system on when the temperature is below
60°, you may damage the compressor.
|
Turn the
fan switch to "auto" and set the thermostat below the room
temperature (76° to 78° is recommended). The fan and condensing
unit should come on, unless there is a time delay, which may slow
its start. |
|
Let the
system run for eight to ten minutes to balance the temperature in
the ductwork. Check the temperature at the supply and return
registers. The temperature at the supply register should be 14° to
20° Fahrenheit cooler than at the return ducts or current room
temperature. |
|
* If the
temperature differential is more than 20°, it indicates restricted
air. This points to three possible problems: 1) a dirty filter, 2)
improper ductwork, or 3) a fan that is sized wrong, not working
properly, or moving too slowly. |
|
* If it
is less than 14° differential, the possible causes are 1)
refrigerant loss, 2) a dirty coil, 3) a laboring compressor, 4) an
oversized fan, or 5) a deficient return air system. |
|
There
are two copper lines going from the condensing unit on the
exterior to the air handler on the interior. The smaller line is
the liquid or high-pressure line and will be warm, not hot, to the
touch when it is operating properly. The larger line covered with
insulation is the suction or low pressure line and will be cold to
the touch. The suction line should be "sweating" or condensing,
the way a glass of iced tea "sweats." It should not be forming
"ice." |
|
|